50 gallon UTRS Series Day Tank
Standard Day Tank with Open 150% Top Containment Basin
The Tramont TRS Series is the industry standard in day tank systems. In addition to the precision engineering and quality construction that goes into all of our systems, the TRS Series features the exclusive Tramont System 2000PLUS™ Electronic Control Module (ECM).
Tank and Control Description:
- Tramont UTRS RB Series diesel fuel tank is a steel rectangular tank with an open top fuel containment basin. Tramont System 2000Plus is an Electronic Control Module (ECM) featuring a microprocessor-based fuel level control and monitoring system. The ECM supervises all performance parameters of the day tank.
Standard Features:
- 1/3 HP, 1 phase, 115 VAC, 60 Hz thermally protected motor.
- 2GPM, high lift gear pump with 3/8” NPT inlet discharge.
- System 2000PLUS™ ECM.
- Heavy gauge steel construction.
- Gray painted exterior, rust-inhibitor coated interior.
- Removable, nonconductive cover.
- Tank 1” NPT fittings are engine supply, engine return, overflow and
alternate engine return. Other fittings include 2 ” NPT for normal vent,
NPT sized as appropriate for emergency vent, and on 3/8” NPT basin drain
for tanks through 275 gallons, 1” NPT for larger tanks. (If tank includes
containment basin, alternate engine fitting is omitted and drain is provided
on basin only).
Square 4 1/2” inspection port located below electric controls. - Emergency pressure relief vent cap – Insure adequate venting and pressure relief inner tank under extreme temperature and emergency conditions.
- Atmospheric vent cap accommodates normal venting – Accommodates normal venting (oversized 2” vent)
- Leak detection switch – Top mounted, annunciates a contained fuel leak at ECM control panel
Construction:
Tank is pressurized at 3 psi and leak checked to ensure integrity of weld seams
per UL 142 standards prior to shipment. Tanks are constructed of heavy gauge
steel. The tank design has been tested extensively under conditions far in excess
of normal use. The open top 150% containment basin is leak checked through the
application of zyglow to the interior of the containment tank.
In addition, tanks are pressure washed with an iron phosphate solution and then finished with an acrylic primer and gray enamel paint (additional colors available). Tank interior is coated with a solvent-based rust preventative.
UL and National Standards:
- Tramont UTRS Series dual wall day tanks are constructed in accordance with the following standards:
- Underwriters Laboratories Inc.
- Tank Standard – UL 142 Steel Aboveground Tanks for Flammable and Combustible Liquids (UL Listed under File MH13710) - ECM Standard
- UL 508 Industrial Control Equipment (UL Listed under File E116902)
- NFPA 30 – Flammable and Combustible Liquids Code
- NFPA 37 – Standard for Installation and use of Stationary Combustible Engine and Gas Turbines
- NFPA 110 – Standard for Emergency and Standby Power Systems